beautypg.com

MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 59

background image



MITSUBISHI ELECTRIC 9800A SERIES UPS

Page Number:

3-26

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

C)

Bypass Operation Procedure

UPS

1. Check for “SYNC” on the LCD.
2. Press the "START/STOP MENU" from the LCD Main Menu.
3. Press the "STOP" key on the LCD.

** Transfer from bypass to inverter.

UPS

1. Press the "START/STOP MENU" from the LCD Main Menu.
2. Press the "START" key on the LCD.

Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start or stop operation can only be performed remotely. If local inverter start or stop operation
is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select
“LOCAL” mode for the purpose of this stop procedure.