MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual
Page 34
MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-1
3.0 INSTALLATION AND OPERATION
3.1 Transportation and Installation
TABLE 3.1 How to transport and install the system
Transportation
Installation
Transport unit with forklift.
Carry with overhead crane using
eyebolts provided.
Using the pre drilled holes (4 - 24) in the
UPS channel base, anchor the unit using
appropriate hardware. (Not provided)
Note :
Do not transport in a horizontal position. Cabinets must be maintained
upright within +/- 15° of the vertical during handling
.
3.2 Installation Procedure
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA)
100
150
225
300
375
500
750
Weight
(lb.)
2100 2820 3310 4990 5250 6930 9655
B) Minimum clearance required for ventilation
Right side
25 mm (not required when sidecars are used)
Left side
25 mm (not required when sidecars are used)
Back side
0.0 mm
Top side
600 mm (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
1000 mm 100kVA, 150kVA, 225kVA
1075 mm 300kVA, 375kVA, 500kVA, 750kVA
Sides
0.0 mm
Rear
0.0 mm