beautypg.com

MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 35

background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-2

D) External Battery Supply

Please refer to the following when installing and maintaining batteries:

1. The customer shall refer to the battery manufacturer's installation manual for

battery installation and maintenance instructions.

2. The maximum permitted fault current from the remote battery supply, and the

DC voltage rating of the battery supply over-current protective device are
shown in Table 3.3.

TABLE 3.3 Maximum Permitted Fault Current

UPS CAPACITY

(kVA)

DC VOLTAGE

RATING (V)

MAXIMUM PERMITTED

FAULT CURRENT (A)

100 480 25000

150 480 25000

225 480 25000

300 480 25000

375 480 25000

500 480 25000

750 480 25000

3.3 Procedure for Cable Connections *

1. Confirm the capacity of the UPS being installed. Identify the input/output power
terminal blocks as shown in the appropriate Figures 3.1 through 3.2-a~g,Figure 3.3.

2. Connect the internal control wire and power wire.

(1) Control wire Inter-connect

1. CB2 NO Auxiliary to terminal TN2

-

23, 24.

2. CB2-UVT to terminal TN2

-

21, 22.

(2) Power wire Inter-connect

a.) From user’s distribution panel

1. X1 (A-phase) to A bus bar in UPS rectifier section.
2. X2 (B-phase) to B bus bar in UPS rectifier section.
3. X3 (C-phase) to C bus bar in UPS rectifier section.