OWNERS / TECHNICAL MANUAL

Page Number:

3-4


(3) Connect the external signal terminal block as desired. Refer to section 2.4 and

Figure 2.15 for functional description. 2mm

2

, or less, shielded conductor is

recommended.

NOTES:

1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and

"CB3" are open before energizing UPS.

2. UPS power terminals are supplied with stud type fittings. It is recommended

that compression lugs be used to fasten all input/output power cables.



6.

Procedure for Cable Connections for Parallel System
(1) Confirm the number of units to be connected in parallel. Identify the input/output

power terminal blocks and control wire connections for parallel systems as shown
in the appropriate Figures 3.4a~c.

(2) Connect the external control wire and power wire.

a.) Control wire connection

Parallel configuration Wiring (Refer to Figure 3.4a~c )

- Critical Load Cabinet (CLC) TB1 to UPSn IOAU-04,TN2.

- Parallel Control CN92, CN93, In, Out cables between UPS modules

b.) Power wire connection

From UPS AC Output Terminals to CLC (Refer to Figure 3.4a~c)