MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual
Page 20
MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-14
TABLE 1.3 Detail of Specifications
Rated Output kVA
100
150
225
300
375
500
750
Rated Output kW
80
120
180
270
338
450
675
AC INPUT
Configuration
3 phase, 3 wire
Voltage
277/480 V, 346/600 V +15% to -15%
Frequency
60 Hz +/-5%
Reflected Current THD
6% max. at 100% load; 9% max. at 50% load
STATIC BYPASS INPUT
Configuration
3 phase, 4 wire
Voltage
277/480 V, 346/600 V +/-10%
Frequency 60
Hz
BATTERY
Type Lead
Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 4 wire
Voltage
277/480 V, 346/600 V
Voltage Stability
+/-
1%
Frequency 60
Hz
Frequency Stability
+/-
0.05% in free running mode
Power Factor
0.8 nominal
0.9 nominal
Power Factor range
0.8 to 1.0 lagging (within output kW rating)
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-
2% maximum at 100% load step
+/-
1% maximum at loss/return of AC power
+/-
5% maximum at load transfer to/from static bypass
Transient Recovery
Less than 20ms
Voltage Unbalance
1% maximum at 100% unbalanced load
Phase Displacement
1deg. maximum at 100% load
Inverter Overload
125% for 10 minutes; 150% for 1 minute
System Overload
1000% for 1 cycle
(with bypass available)
500% for 1 cycle
(with bypass available)
Bypass Overload
125% for 10 minutes
Withstand Rating
65kA* * : with optional fuse
ENVIRONMENTAL
Cooling Forced
Air
Operating Temperature
32゚F to 104゚F ( 0゚C to 40゚C).
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 to 9000 feet No Derating
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell 5Y7/1 (Beige)