page 36 — Sg1400C3 STudio generaTor • operaTion manual — rev. #0 (10/05/11)

9. If paralleling to another unit and the bus was already

energized from another unit (BUS HOT light already

on), pressing to close GCB button once would initiate

a synchronizing mode. The light above the button will

begin flashing, bring the generator into phase and

automatically close the breaker. Once the breaker

closes, the light above the button would then become

solid and the generators would now be in parallel. As

load is applied, units will share the load proportionally.

CloSing THe enCloSure doorS

1. Close the enclosure doors once the generator has

started (Figure 29). Top vents stay open for proper

ventilation.

Figure 29. Engine Enclosure Doors

2. If access to the controls or other components is

necessary while the engine is running, make sure the

doors are not left open for an extended period of time.

3. To protect the unit from rain, the top intake vent can

be closed by opening the upper front vent door on the

generator enclosure. The front vent will automatically

close the upper roof intake vent. The upper exhaust
vent will remain open.

normal SHuTdoWn proCedure

To shutdown the generator, use the following procedure:

Close

Doors

RAIN DOOR

INTAKE VENT

Warning

never stop the engine suddenly except in an

emergency.

1. Press the GCB control button on the controller

(Figure 30) to open circuit breaker.

Figure 30. Generator Circuit Breaker (Open)

2. Let the engine cool by running it at full speed for 3-5

minutes with no load applied.

3. Press the

STop button (Figure 31) on the controller.

The engine will go to idle mode.

Figure 31. STOP Button

4. Press the

STop button again to shut down the engine.

5. Place the Control Power switch (Figure 32) on the

control panel to the OFF position.

Figure 32. Control Power Switch (OFF)

emergenCY SHuTdoWn proCedure

1. Press the

STop button twice (Figure 31) on the

controller to shut down the engine.

2. Place the main circuit breaker (Figure 30) in the

oFF

position.

Open GCB

PRESS BUTTON

NOTICE

If

STop button is not pressed again, the engine will

remain in idle mode for about an hour then will shut

down.

OFF (DOWN)