Sg1400C3 STudio generaTor • operaTion manual — rev. #0 (10/05/11) — page 33

inSPECtiOn/SEtuP

BaTTerY

This unit is of negative ground.

do noT connect in reverse.

Always maintain battery fluid level between the specified

marks.

do noT over fill. Battery life will be shortened if

the fluid level is not properly maintained. Add only distilled

water when replenishment is necessary.
Check to see whether the battery cables are loose. Poor

contact may result in poor starting or malfunction.

always

keep the terminals firmly tightened. Coat the terminals with

an approved battery terminal treatment compound. Replace

battery with only recommended type battery.
The battery is sufficiently charged if the specific gravity

of the battery fluid is 1.28 (at 68° F). If the specific gravity

should fall to 1.245 or lower, the battery is dead and needs

to be recharged or replaced.
Before charging the battery with an external electric source,

be sure to disconnect the battery cables.

Battery Cable installation

alWaYS make sure that the battery cables (Figure 17) are

properly connected to the battery terminals as shown below.

Figure 17. Battery Connections

CauTion

alWaYS disconnect the negative terminal FirST and

reconnect negative terminal

laST.

When connecting the battery do the following:
1. Place a small amount of battery terminal treatment

compound around both battery terminals. This will

ensure a good connection and will help prevent

corrosion around the battery terminals.

2. Connect the

red cable to the positive terminal of the

battery and the

black cable to the negative terminal

of the battery.

.

alTernaTor

The polarity of the alternator is negative grounding type.

When an inverted circuit connection takes place, the circuit

will short instantaneously resulting in alternator failure.
do noT put water directly on the alternator. Water in the

alternator can cause corrosion and damage.

Wiring

Inspect the generator for bad, worn electrical wiring or

connections. If any wiring or connections are exposed

(insulation missing), replace wiring immediately.

piping and HoSe ConneCTion

Inspect all piping, oil hose, and fuel hose connections for

fatigue, wear and tightness. Tighten all hose clamps and

check hoses for leaks.
If any hose (

fuel or oil) lines are defective, replace them

immediately.

NOTICE

If the battery cable is connected incorrectly, electrical

damage to the generator will occur. Pay close attention

to the polarity when connecting the battery.

CauTion

Inadequate battery connections may cause poor

starting of the generator, and create other malfunctions.