Sg1400C3 STudio generaTor • operaTion manual — rev. #0 (10/05/11) — page 35

StartuP

6. If unit is to be used in parallel with another unit,

interconnect the units. Interconnect the output buses

with suitable power cables to carry full load capacity.

Special male-to-male Camlok cables will be needed.

For 480 V mode, it is recommended that one 4/0 cable

per phase, neutral and ground be used. For 208V

mode, use two 4/0 cables per phase and neutral and

one 4/0 cable for ground. Also connect the parallel

communication cables.

7. Connect the load to the receptacles on the Camlok/

Voltage Output Panel. When the camloks are inserted

into the outlet connector, rotate clockwise until they are

locked in place. Make sure the camloks are connected

securely.

8. Press the MODE button (Figure 25) on the Digital

Controller Display and select manual mode (MAN)

with the arrow keys. Press Enter key when MAN is

highlighted on the screen.

Figure 25. Mode Button (Manual)

STarTing (manual)

1. Press the

STarT button (Figure 26) on the controller

to start the engine.

Figure 26. START Button

2. The engine will go to idle mode.
3. Listen for any abnormal noises. If any abnormalities

exist, shut down the engine and correct the problem.

MAN

PRESS MODE BUTTON

4. To bypass idle mode, press the

STarT button again.

The generator should go to full speed.

5. Verify that the no-load frequency reading on the

control panel frequency display is approximately 60

Hz (1800 rpm).

6. Verify that the voltage reading on the control panel AC

voltmeter display matches the voltage selector switch

position that was selected prior to startup.

7. Press the GCB control button on the controller

(Figure 27) to close circuit breaker.

Figure 27. Generator Circuit Breaker (Closed)

8. Verify that the BUS HOT light on the Camlok/Voltage

Output Panel is on. Voltage is now available at the

receptacles.

Figure 28. Bus Hot Light

NOTICE

If

STarT button is not pressed again, the engine will

remain in idle mode for about an hour then will go to

full speed.

Close GCB

PRESS GCB CONTROL BUTTON

BUS HOT

LIGHT