beautypg.com

MITSUBISHI ELECTRIC TG-2000A User Manual

Page 47

background image

44

3) Select the OC icon, and click on the selected outdoor unit.

Select the icon of the outdoor unit connected to the watt hour meter by clicking on the icon. Then,
click in the cell of the selected outdoor unit. The outdoor unit is now connected to the watt hour meter.

4) Repeat steps 1) t o 3).

Repeat this procedure on each of the outdoor units connected to a watt hour meter. Also, set the
options for every watt hour meter that has an outdoor unit connected to it.

5) Select [OK] button.

When done with these settings, click the [ OK] button.
* If the [Cancel] button is clicked, the settings are interrupted and the screen returns to the initial

window.

Delete Watt Hour Meter Relationships.

Follow these steps to delete the relationship between an outdoor unit and a watt hour meter.

[Procedure]
1) Click on the icon to be deleted.

Click on the icon of the outdoor unit to be deleted.
The relationship between that unit and the watt hour meter is deleted.







8.9.4 Electrical specification of outdoor units (Step 3)

Follow these steps to set the crank case heater capacity
of an outdoor unit connected to a watt hour meter. Do
these steps for all connected outdoor units.

Set the outdoor unit crank case heater capacity.

[Procedure]
1) Select the G-50 number using the “ / ” button.

Using the “ / ” button, select the G-50A number

assigned to the outdoor unit whose crank case heater
capacity is to be set.

2) Set the crank case heater capacity.

Click on the crank case heater capacity cell of each
outdoor unit, and set the capacity (W). Since the
crank case heater capacity is different for each crank
case type, please see the data book or catalog for
details.
* For outdoor units with a unit Model Name set in

the database, the crank case heater capacity is
displayed automatically.

3) Repeat steps 1) and 2).

Repeat these steps for every unit.

4) Select [OK] button.

When finished setting the crank case heater
capacity, click the [ OK] button.
* If the [Cancel] button is clicked, the settings are

interrupted and the screen returns to the initial
window.


Note:

• If a unit has not been assigned to a watt hour meter, a warning is displayed. Correct the setting to

proceed.

• This setting window is not displayed for Without WHM connection proportionally divided electric

charge (manual input of the electric amount).

Model Numbers

Crank Case

Heater Capacity

PUY-(P)200/250YMF -C
P U H Y-( P ) 2 0 0 /250YMF-C
P H R Y-(P)200/250YMF-C

6 2 W

P U H Y-P400/500YMF -B

1 0 1 W

P U H Y-(P)600/650/700/750

YSMF -B

1 5 7 W

P U R Y-(P)200/250YMF -B
PQRY-P200/250YMF -B

4 5 W

PUMY-P125YMA

0 W

Outdoor Unit Settings window

Select G-50A