beautypg.com

GE AV-300i User Manual

Page 29

background image

29

The speed during acceleration with maximum current is not linear

Reduce the Speed I and Speed P proportionally. If this does not lead to an improvement,
optimize the regulator per the instruction book.

Speed oscillating

Check Speed P and Speed I parameter

If the operating point is in the constant Hp range, check the Flux P and Flux I parameters

Incorrect value for Rotor resistance

Remedy: Optimize the tuning as described in the AV-300i instruction book.

Drive not reacting to adaptive speed regulation

Adaptive speed regulation not enabled. Enable spd adap = Enabled

Adap reference not assigned to an analog input

Motor potentiometer function not executed

Function not enabled. Enable motor pot = Enabled

With operation via the terminal strip: Motor pot up and/or Motor pot down and Motor pot
sign
were not assigned to digital inputs

Jog operation not possible

A start command is still present

Function not enabled. Enable jog = Enabled

With operation via terminal strip: Jog + and/or Jog - were not assigned to digital inputs.

Internal speed reference values not actuated

Function not enabled. Enab multi spd = Enabled

With operation via terminal strip: Speed sel 0, Speed sel 1 and Speed sel 2 were not assigned
to digital inputs.

Multi-Ramp function not reacting

Function not enabled. Enab multi rmp = Enabled

With operation via terminal strip: Ramp sel 0 and Ramp sel 1 were not assigned to digital
inputs