Qs.4.4 initial configuration procedure, Initial, Onfiguration – GE QS24 UR User Manual
Page 21: Rocedure, Qs-17, Onfiguring, Witch, Ip a, Ddress, Ubnet
QUICKSTART GUIDE
UR SWITCH MODULE – QUICKSTART GUIDE
QS–17
FIGURE QS–12: UR Switch Module Wiring Diagram
QS.4.4 initial Configuration Procedure
CAUTION
Ensure Switch is configured before connecting to network devices.
A suitable IP address and subnet mask must be assigned to both the Switch and the UR
relay for correct operation. The Switch has been shipped with a default IP address of
192.168.1.2 and a subnet mask of 255.255.255.0. Consult your network administrator to
determine if the default IP address, subnet mask or default gateway needs to be modified.
QS.4.5 Configuring the Switch IP Address and Subnet Mask using EnerVista UR Setup Software.
In our example configuration of both the Switch’s IP address and subnet mask must be
changed to 3.94.247.229 and 255.255.252.0 respectively. The IP address, subnet mask and
default gateway can be configured using either EnerVista UR Setup software, the Switch’s
Secure Web Management (SWM), or through the console port using CLI.
In this example EnerVista UR setup software will be used.
Z
From the Product setup menu select Communications > Ethernet
Switch > Configure IP.
Z
Enter the Switch’s MAC address (located on the module), IP address
that you want to set in the switch, and Subnet Mask.
HEAVY COPPER CONDUCTOR
OR BRAIDED WIRE
SWITCHGEAR
GROUND BUS
UR SERIES
PROTECTION SYSTEM
AC or DC
AC or DC
Optional UR-2S
or UR-2T
Switch Module
Control Power
+
LOW
+
HIGH
F
I
L
T
E
R
S
U
R
G
E
B8b B8a
-
B6a B6b B5b
-
NOTE:
14 gauge stranded
wire with suitable
disconnect devices
is recommended
GND
+
-