Electrical wiring, Caution, Warning – Goodman Mfg IO-367B User Manual

Page 8

background image

8

CPC Weights

(lbs)

CPC Weights

(lbs)

15 Tons

20 Tons

Corner Weight - A

580

655

Corner Weight - B

540

535

Corner Weight - C

475

510

Corner Weight - D

440

420

Unit Shipping Weight

2150

2235

Unit Operating Weight

2035

2120

X (Inches)

60"

58"

Y (Inches)

43"

40"

DATA

NOTE: These weights are without accessories installed.

T

O

PREVENT

SEVERE

DAMAGE

TO

THE

BOTTOM

OF

THE

UNIT

,

DO

NOT

FORK

LIFT

UNIT

AFTER

WOOD

STRUTS

HAVE

BEEN

REMOVED

.

CAUTION

Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using
curb as a fulcrum, lower opposite end of the unit until entire
unit is seated on the curb. When a rectangular cantilever
curb is used, care should be taken to center the unit. Check
for proper alignment and orientation of supply and return
openings with duct.

R

IGGING

R

EMOVAL

T

O

PREVENT

DAMAGE

TO

THE

UNIT

,

DO

NOT

ALLOW

CRANE

HOOKS

AND

SPREADER

BARS

TO

REST

ON

THE

ROOF

OF

THE

UNIT

.

CAUTION

Remove spreader bars, lifting cables and other rigging equip-
ment.

ELECTRICAL WIRING

HIGH VOLTAGE!
D

ISCONNECT

ALL

POWER

BEFORE

SERVICING

OR

INSTALLING

THIS

UNIT

. M

ULTIPLE

POWER

SOURCES

MAY

BE

PRESENT

. F

AILURE

TO

DO

SO

MAY

CAUSE

PROPERTY

DAMAGE

,

PERSONAL

INJURY

OR

DEATH

.

WARNING

HIGH VOLTAGE!
T

O

AVOID

PERSONAL

INJURY

OR

DEATH

DUE

TO

ELECTRICAL

SHOCK

,

DO

NOT

TAMPER

WITH

FACTORY

WIRING

. T

HE

INTERNAL

POWER

AND

CONTROL

WIRING

OF

THESE

UNITS

ARE

FACTORY

-

INSTALLED

AND

HAVE

BEEN

THOROUGHLY

TESTED

PRIOR

TO

SHIPMENT

.

C

ONTACT

YOUR

LOCAL

REPRESENTATIVE

IF

ASSISTANCE

IS

REQUIRED

.

WARNING

T

O

PREVENT

DAMAGE

TO

THE

WIRING

,

PROTECT

WIRING

FROM

SHARP

EDGES

. F

OLLOW

NATIONAL

ELECTRICAL

CODE

AND

ALL

LOCAL

CODES

AND

ORDINANCES

. D

O

NOT

ROUTE

WIRES

THROUGH

REMOVABLE

ACCESS

PANELS

.

CAUTION

C

ONDUIT

AND

FITTINGS

MUST

BE

WEATHER

-

TIGHT

TO

PREVENT

WATER

ENTRY

INTO

THE

BUILDING

.

CAUTION

For unit protection, use a fuse or HACR circuit breaker that is
in excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED
THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN
ON UNIT DATA PLATE.

All line voltage connections must be made through weather-
proof fittings. All exterior power supply and ground wiring
must be in approved weatherproof conduit.

The main power supply wiring to the unit and low voltage
wiring to accessory controls must be done in accordance with
these instructions, the latest edition of the National Electrical
Code (ANSI/NFPA 70), and all local codes and ordinances.
All field wiring shall conform with the temperature limitations
for Type T wire (63°F/35°C rise).

The main power supply shall be three-phase, three wire. The
unit is factory wired for the voltage shown on the unit’s data
plate.

NOTE: If supply voltage is 208V, all leads on primary of trans-
former TRANS1 must be moved from the 230V to the 208V
tap.

Main power wiring should be sized for the minimum wire
ampacity shown on the unit’s data plate. Size wires in accor-
dance with the ampacity tables in Article 310 of the National
Electrical Code. If long wires are required, it may be neces-
sary to increase the wire size to prevent excessive voltage
drop. Wires should be sized for a maximum of 3% voltage
drop.