beautypg.com

Goodman Mfg IO-367B User Manual

Page 16

background image

16

APPENDIX A BLOWER PERFORMANCE DATA

BELT DRIVE - STANDARD

NOTES:

High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.

Unit factory shipped with sheave set at 2.5 turns open.

Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.2

---

---

---

---

---

---

---

---

---

---

7203

2.18

6718

1.94

0.4

---

---

---

---

---

---

7306

2.54

6777

2.14

6257

1.80

5711

1.66

0.6

---

---

7477

2.97

6899

2.51

6323

2.10

5716

1.72

5103

1.39

---

0.8

7112

2.96

6467

2.46

5795

2.01

5101

1.61

---

---

---

---

---

---

1.0

5983

2.38

5190

1.89

---

---

---

---

---

---

---

---

---

---

1.2

4426

1.71

---

---

---

---

---

---

---

---

---

---

---

---

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.2

---

---

---

---

---

---

---

---

---

---

---

---

9664

4.05

0.4

---

---

---

---

---

---

---

---

9570

4.08

9197

3.82

8702

3.51

0.6

---

---

---

---

---

---

9038

3.82

8460

3.46

7949

3.14

---

---

0.8

---

---

8171

2.93

7630

3.70

7068

2.79

---

---

---

---

---

---

1.0

---

---

7901

2.85

7203

3.42

---

---

---

---

---

---

---

---

1.2

7344

4.35

---

---

---

---

---

---

---

---

---

---

---

---

CPC240 STANDARD BELT DRIVE

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

6

CPC180 STANDARD BELT DRIVE

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

6