INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1.1
The chimney or flue system must comply with the rules in
force, and must be a minimum of 127mm in diameter. (5").
1.2
The minimum flue height for the appliance must be 3
metres (10ft). Any horizontal flue run from the rear outlet
must not exceed 100mm from the back of the appliance.
1.3
The chimney or flue must be free from any obstruction. Any
damper plates must be removed or secured in the fully
open position, and no restrictor plates fitted.
1.4
The chimney must be swept prior to the installation, but it
need not be swept if it can be seen the chimney is clean
and unobstructed throughout its entire length.
1.5
A5" (127mm) liner must be used if fitting the stove into an
existing brick built chimney.
Larger lined flues can work, but in some instances could
cause cold start flue problems resulting in nuisance
shutdown. Lined flues above 7" (175mm) are not
recommended.
1.6
Due to recent changes to European chimney standards,
new flues and chimneys are described by their temperature,
pressure and resistance to corrosion, condensation and fire.
To assist in identifying the correct flue system, the minimum
flue specification is shown in the Technical Specification.
Existing chimneys are not covered by this system.
2.1
Consult the rules in force.
Note: This appliance does not normally require any
additional ventilation when installed in G.B.
3.1
Before installation, ensure that the local distribution
conditions (identification of the type of gas and pressure)
and the adjustment of the appliance are compatible.
3.2
Ensure the gas supply is capable of delivering the required
amount of gas, and is in accordance with the rules in force.
3.3
Soft copper tubing and soft soldered joints can be used but
must not be closer than 50mm to the base of the tray.
3.4
A means of isolating the gas supply to the appliance must
be provided independent of any appliance control.
3.5
All supply gas pipes must be purged of any debris that may
have entered, prior to connection to the appliance.
4.1
This appliance must stand on a non-combustible hearth that
is at least 12mm thick, and project a minimum of 50mm
from the base of the stove in all directions, Diagram 1.
4.2
This appliance must not be installed in a room that contains
a bath or shower.
4.3
The stove is not suitable for installation against a
combustible wall; all combustible materials must be
removed from the area behind the stove.
4.4
Ensure you comply to all minimum clearances to
combusible materials. See Diagram 2 & 2A.
In a non-combustible recess be careful to allow enough
clearance at the sides and rear of the stove to perform
spillage tests and reach the controls
.
2A
AR0531
2
AR0522
150
225
853
150
1
A = 653
B = 501
C = 12
AR0604
4. APPLIANCE LOCATION
3. INSTALLATION OF THE GAS SUPPLY
2. VENTILATION
1. FLUE AND CHIMNEY REQUIREMENTS