7, f – GE EPM 3000P User Manual
Page 44

Chapter 11 Phase Reversal & Phase Imbalance Set Limits/Relays
11.3 G
ROUP
7, F
UNCTION
0: V
OLTAGE
P
HASE
R
EVERSAL
D
ETECTION
Ö
To change the PHASE REVERSAL settings, follow these steps:
NOTE: PRESS MAX/MIN/LIMITS, AT ANY TIME, TO CANCEL BEFORE STORING THE LAST DIGIT OR SWITCH
.
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
7.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
70.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
_
__
Step 1:
a. Enter Group Level of Programming Mode
(see Chapter 2).
b. Press MAX/MIN/LIMITS until 7. appears in upper
display.
c. Press VOLTS to activate the Group.
Ö
70. appears in upper display.
Ö
Lower display indicates current settings for
Enable/Disable Phase Reversal Detection.
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
70
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
__
_
Step 2:
a. Press VOLTS once.
Ö
Three dashes appear in lower display.
b. Press PRINT/PROG to change current Set
Above/Below, Trip Relay 1, and Trip Relay 2 settings.
Ö
This toggles the segments UP (above limit) or DOWN
(below limit).
c. Press VOLTS to store.
39
GE Industrial Systems