Suggested Bid Form Specifications (continued)

Heat pump unit shall include Reverse Cycle Defrost that

automatically begins a defrost cycle when microprocessor

determines criteria for defrosting has been met. Defrosting

shall be accomplished by systematically ceasing heat pump

operation, pausing to allow internal refrigerant pressures

to equalize, then operating the compressor with the flow of

refrigerant reversed to allow the hot gas to flow through the

outdoor coil melting the accumulated frost. The unit shall

automatically resume heat pump operation, after pausing

to allow refrigerant pressures to equalize, at conclusion of

defrost cycle.
The unit shall be equipped with a temperature-activated

drain valve to allow water generated in heat pump operation

and defrost cycles to drain into the wall case rather than

being deposited on the outdoor coil.
In the event of compressor failure during heat pump

operation, The unit shall automatically switch to electric

resistance heat to maintain selected room temperature

regardless of outdoor temperatures.
The unit shall have a switch concealed from room occupant

to allow heat pump operation to be overridden and heat

provided by electric resistance heat regardless of

outdoor temperature.
In the event of compressor failure during heat pump

operation, unit shall automatically switch to electric

resistance heat to maintain selected room temperature

regardless of outdoor temperatures.
Specifications for Optional Internal Condensate Removal

(ICR) system for 3900 or 5800 series heat pump units.
The unit shall have a factory-installed Internal Condensate

Removal (ICR) system to permit unit to automatically dispose

of heat pump generated condensate water with no overflow

to outdoors during heating under outdoor ambient of 55°F Dry

Bulb, 90% Relative Humidity; indoor ambient 70°F Dry Bulb,

52% Relative Humidity, for four hours of continuous run time.
(Wall Cases and Grilles are needed for new installations.)
(Alternate specification for steel wall case.)
Wall Case. The wall case shall be constructed of heavy-gauge,

insulated, zinc-coated phosphated steel with a protective

baked-on enamel finish. Bottom critical points of the steel

wall case shall be coated with petroleum microcrystalline

wax for added corrosion protection and shall meet ASTM

B-117, 1800-hour hot air aerated salt spray test.
(Alternate specification for molded wall case.)
Wall Case. The wall case shall be constructed of a

non-corroding fiberglass-reinforced polyester compound.
Cases shall be installed through exterior walls where

shown on the plans and shall be installed per manufacturer’s

installation instructions. In no instance shall fasteners be

used through the bottom in order to retain the water integrity

of the bottom of the wall case.
Outside weather panels shipped with the cases shall remain

in place until the outdoor air louvers and chassis are installed,

at which time they are to be removed and discarded by

the installer.
Outside Grille. Each unit shall be equipped with a standard

exterior grille that has been designed to allow unit operation

in high ambient conditions. Grilles shall be of material and

design specified.

Special grilles or customer louver sections to be supplied by

others will conform to a minimum of 65% free area to allow

for proper unit operation and shall be submitted to the PTAC/

PTHP manufacturer, if requested, for feasibility and airflow

characteristics.
Specifications for Sub-Base (if required)
Sub-Base. Each unit shall have a field-installed UL-listed

electrical sub-base. The sub-base shall be attached to the

lower inside flange of the wall case prior to installation in the

exterior wall. It shall include adjustable screws at the bottom

corners to permit exact leveling of the wall case. The sub-base

shall have a factory-installed receptacle to allow unit line cord

to plug into mating receptacle and shall have a chaseway to

contain and conceal the line cord. The sub-base shall have side

panels adjustable from a minimum of 2-/8" to a maximum of

1-/4" to enclose the area under the wall case.
Weather Resistance. Complete unit including outside louver

shall be submitted to an independent agency for weather

resistance tests.
Air infiltration test to be conducted in accordance with

ASTM E28-91. With static air pressure differential of

1.57 lb./ft.

2

(." H

2

O) equivalent to 25 mph wind, allowable

air infiltration shall not exceed 7 ft.

/min.

Approvals. Units shall be certified under the ARI and cUL

certification program and listed by UL.
Service. Submit complete information with bid covering

service availability to whom service on units will be assigned,

along with complete address and phone number, including

phone number of emergency service personnel.
Start-Up, Adjust, Demonstrate. Contractor shall be responsible

for the initial starting of units, adjustments thereto, etc., to

place the units in required operating condition. Contractor

shall demonstrate to the owner or his representative the

operation of units for both summer and winter functions.
Warranty. The warranty shall be a full one-year parts and

labor on the entire unit, plus an additional full four years

parts and labor for the sealed refrigerating system, including

service call for diagnosis and transportation to and from

service shop (if necessary) at no charge to the customer.

The warranty shall also include a limited second through

fifth year parts only warranty for fan motors, switches,

thermostat, heater, heater protectors, compressor overload,

solenoids, circuit boards, auxiliary controls, thermistors,

frost controls, ICR pump, capacitors, varistors and indoor

blower bearing.
Installation Responsibility. Units shall be installed

according to the manufacturer’s recommendations and the

manufacturer shall not be responsible for unit failure as a

result of improper installation, or unit performance when

installed with accessories not approved by the manufacturer.