Suggested bid form specifications – GE Monogram 5800 Series User Manual

Page 52

background image

52

The following are suggested specifications for the Zoneline

®

2900 Series Packaged Terminal Air Conditioner, the 3900

Series Packaged Terminal Heat Pump and the 5800 Series

Packaged Terminal Heat Pump.
The contractor will furnish Packaged Terminal Air Conditioners

of the sizes and capacities shown on the schedule and in the

specifications. The units shall be located as shown on the

drawings and each shall consist of a chassis, room cabinet,

wall case, sub-base if specified, and outdoor grille.
Units shall be listed by UL, and ARI and cUL certified as to

capacity and efficiency and shall be GE Zoneline

®

models

or equal. Unit dimensions shall not exceed 42-1/8" wide and

16-1/4" high with room cabinet in place.
Units shall be designed to operate on (208) (20) (265) volts,

60 Hz., single-phase power.
Chassis. The air conditioner chassis shall be the standard

product of the manufacturer and shall be shipped in protective

cartons to prevent damage. Cartons shall be appropriately

marked at the factory with wording sufficient to warn handlers

against improper stacking, up-ending, rolling or dropping.
The chassis shall be the slide-in type, ready to operate after

installation.
Each shall consist of the following sections and components:
• Each unit shall have a matching, easily removable,

textured finish, wrap-around room cabinet molded of high-

temperature styrene to resist corrosion and damage. The

room cabinet shall have slide-out washable filters accessible

without requiring removal of room cabinet from chassis;

• Hermetically sealed refrigerant system with external

vibration isolated rotary-type compressor, condenser and

evaporator coils and capillary refrigerant control. Cooling

shall be possible to outdoor temperature of 5°F without

damage to the compressor. Airflow system consisting of one

permanently lubricated two-speed fan motor for the outdoor

fan and a separate permanently lubricated two-speed fan

motor for the indoor fan. Outdoor fan shall be multi-blade

axial-flow design made of non-corrosive material. Indoor fan

shall be of a design to optimize airflow and operating sound.

All motors on the exterior side of the weather barrier shall

be of an enclosed design to reduce the effects of moisture

and corrosion;

• Line-cord connected units shall require a line cord power

connection kit with integral Leakage Current Detection

and Interruption device or Arc Fault Current Interrupter

as required by National Electrical Code and Underwriters

Laboratories. The unit shall have a universal resistance

heater with output determined by connection to the power

source with the appropriate power connection kit to provide

specified heat output;

• A fan-cycle switch to permit continuous fan operation or

fan cycle operation, independently selectable for heating

and cooling operation;

• Fan-only operation in either high or low fan speed selectable

by room occupant;

• A positive cooling condensate disposal system which meets

the test requirements of applicable A.R.I. Standard 10-04

(for Packaged Terminal Air Conditioners) and 80-04 (for

Packaged Terminal Heat Pump) (80°F dry bulb, 75°F wet

bulb, 80% relative humidity);

Suggested Bid Form Specifications

• Condenser and evaporator coils to be constructed of copper

tubing and aluminum plate fins designed to achieve EER and

COP rating of the unit;

• Indoor and outdoor airflows that match the capacity of the

coils for efficient heat transfer. Water blow-off shall not occur

on the indoor coil;

• Adjustable indoor discharge air louvers that provide a 50° off

vertical air pattern with an alternate position to provide a 40°

off vertical air pattern;

• Easily accessible controls for selection of unit operation

and thermostat setting. Controls shall be covered by a

hinged door;

• Air discharge area accessible for cleaning without tools

when room front is removed for 2900 and 900 Series;

• Positive-closing, manually controlled, three-position fresh-air

vent capable of providing selection of fully open, partially open

or closed setting. Vent door is to be secured for shipping;

• Solid-state thermostat control to sense room temperature;
• Electronic temperature limiting with seven independent

heating and cooling settings to limit maximum and minimum

temperatures without restricting movement of thermostat

control knob;

• Freeze Sentinel

to automatically activate the electric

resistance heater and fan motor to warm and circulate indoor

air to help prevent damage due to freezing temperatures.

Freeze Sentinel shall operate as long as unit is connected

to powered electrical circuit and unit shall provide ability for

owner to defeat the Freeze Sentinel operation;

• Heat Sentinel to automatically activate air conditioner

operation when the unit is in the STOP setting when the

room temperature warms to 85ºF and turns air conditioner

operation off when the room temperature cools to 80°F, if

selected by owner;

• Compatible with two-wire Central Desk Control systems;
• Remote Thermostat compatibility with Class 2 remote

thermostat;

• Connections to interface with a transfer fan to move air into

another room;

• Connections to interface with occupancy sensors;
Unit shall have means of electrical connection listed by

Underwriters Laboratories and compatible with the unit’s

required voltage and ampacity in conformance with National

Electrical Code

®

(NEC) and local codes.

Additional specifications for GE Zoneline

®

900 or 5800 Series

Packaged Terminal Heat Pump
Heat pump units shall provide operation that will either:

A) automatically phase-in partial electric resistance heat,

if outdoor temperature is below 46°F, simultaneously with

heat pump if heat pump alone is unable to maintain room

temperature; or B) use partial electric resistance heat

simultaneous with heat pump operation any time the outdoor

temperature is below 45°F. Selection of A or B operation is

made by means of a selector switch concealed from room

occupant. In either A or B operation, the unit will switch

to full resistance heat if room temperature continues to

decline or the outdoor temperature falls below 25°F. If the

outdoor temperature is above 46°F, unit will lock-out electric

resistance heat and operate on heat pump only.