Actwinpro configuration, Actwinpro – Guardian Technologies ACT1000 User Manual
Page 30
ACTWinPro Configuration
A B 0V
TX
RX
NETWORK
D
O
O
R
S
A
B
0V
SE
RIA
L/P
RIN
TE
R
0V
DTR
RED
GREEN
ACTWinPro
From the Installer Menu, do the following:
1. Factory Default the controller.
2. Go to the Communications menu and Set Address. If there is only 1
controller, set the address to 1. For more than 1, assign each controller
a unique address, starting at 1.
3. Set Direct Connect to Yes if the PC is connected directly to one controller (as
shown above). Set to No if it is a networked system. For more than one
controller, an RS-485 Network Interface is required.
4. Connect the controller(s) to the PC.
5. From ACTWinPro, configure a new database.
6. Follow the database creation wizard.
7. Ensure that Comms is set up correctly.
8. Connect to the controllers.
Click here to configure Comms
Select if Direct Connect or
Networked
Select if Serial Port or
Modem or TCP/IP Connection
Select COM port and Speed
Click here to Connect
ACT2000
Page 27 of 32
Direct Connect Cable