Troubleshooting – unit – Greenheck Fan 455924 ERV-522 User Manual

Page 33

background image

33

Energy Recovery Ventilator

Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.

Symptom

Possible Cause

Corrective Action

Blower fails to

operate

Blown fuse or open circuit breaker.

Replace fuse or reset circuit breaker and check
amps.

Defective motor or capacitor.

Replace.

Motor starter overloaded.

Reset starter and check amps.

Electrical.

Check for On/Off switches. Check for correct
supply voltage.

Drive.

Check for broken or loose belts. Tighten loose
pulleys.

Motor starters

“chatter” or

do not pull in

Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).

Shorten wiring run to mechanical room or
install a relay which will turn unit on/off. Consult
Factory for relay information.

Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the coil.

Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.

Motor over amps

CFM too high.

Check cfm and adjust drives if needed.

Static pressures are higher or lower than
design.

If higher, ductwork should be improved.
If lower, fan rpm should be lower.

Blower rotation is incorrect.

Check rotation and reverse if necessary.

Motor voltage incorrect.

Check motor nameplate versus supplied
voltage.

Motor horsepower too low.

See specifications and catalog for fan curves to
determine if horsepower is sufficient.

Shorted windings in motor.

Replace motor.

Low airflow (cfm)

Unit damper not fully open.

Adjust damper linkage or replace damper motor.

System static pressure too high.

Improve ductwork to eliminate losses using
good duct practices.

Blower speed too low.

Check for correct drives and rpm with catalog
data.

Fan wheels are operating backwards.

For 3-phase, see Direction of Fan Wheel
Rotation under Unit Start-Up section.

Dirty filter or energy wheel.

Follow cleaning procedures in Routine
Maintenance section.

Leaks in ductwork.

Repair.

Elbows or other obstructions may be
obstructing fan outlet.

Correct or improve ductwork.

Belt slippage.

Adjust belt tension.

High airflow (cfm)

Blower fan speed too high.

Check for correct fan rpm. Decrease fan speed
if necessary.

Filter(s) not in place.

Install filters.

Insufficient static pressure (Ps) (airflow
resistance).

Induce Ps into system ductwork. Make sure
grilles and access doors are installed. Decrease
fan speed if necessary.

Troubleshooting – Unit