Sensors mounted by factory – Greenheck Fan 455924 ERV-522 User Manual

Page 21

background image

21

Energy Recovery Ventilator

Temperature Sensors - 1K Ohm RTD

Drawing Labels

Terminal Strip Labels

OAI

OA/Supply Inlet Temp

OAAW

OA After Wheel

RAI

RA/Exhaust Inlet Temp

OAD

Supply Discharge Temp

EAW

Exhaust After Wheel Temp

Pressure Sensors (analog or digital)

Drawing Labels

Terminal Strip Labels

OAF-P

OA/Supply Filter Pressure

OAW-P

Outdoor Air Wheel Pressure

RAF-P

RA/Exhaust Filter Pressure

EW-P

Exhaust Wheel Pressure

Amp - Current Sensors (analog or digital)

Drawing Labels

Terminal Strip Labels

OAF-A

Supply Fan Amps

EF-A

Exhaust Fan Amps

Sensors Mounted by Factory

Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for
the controls contractor to connect the Building Management System for monitoring purposes.

RAI

RAF-P

RA

FILTER

OAAW

OAF-A

OAD

SUPPLY

BLOWER

TO

INSIDE

FROM

INSIDE

EW-P

OAW-P

ENERGY WHEEL

EAW

EF-A

OAI

OA

FILTER

OAF-P

TO

OUTSIDE

FROM

OUSTIDE

EXHAUST

BLOWER