Energy Recovery Ventilator

Economizer Application/Operation

The energy recovery wheel operation can be altered
to take advantage of economizer operation (free
cooling). Two modes are available:

1. De-energizing the wheel
2. Modulating the wheel

A field supplied call for cool (Y1) is required.

De-energizing the wheel is accomplished with a signal
from a Temperature or Enthalpy sensor mounted
in the air intake compartment. This primary sensor
will de-energize the energy wheel when the outdoor
air temperature (factory default is 65ºF) or enthalpy
(factory default is the ‘D’ setting) is below the field
adjustable set point. An Override temperature
sensor is also furnished in the outdoor air intake
compartment to deactivate economizer mode. The
Override (with field adjustable set point) is set at
some temperature lower than the primary sensor
(factory default is 50ºF). Effectively, the two sensors
create a deadband where the energy recovery wheel
will not operate and free cooling from outside can be
brought into the building unconditioned.

Testing

Temperature Sensor with Override

t 5VSOCPUI5FNQFSBUVSFBOE

Override thermostats down as low
as they go. The wheel should be
rotating.

t 5VSOUIF5FNQFSBUVSFTFOTPSVQ

as high as it goes, and keep the
Override sensor as low as it will go.
The wheel should stop rotating.

t 5VSOCPUITFOTPSTBTIJHIBTUIFZXJMMHP5IF

wheel should start rotating.

t 4FUUIF5FNQFSBUVSFTFOTPSBUEFTJSFEQPJOU

for economizer operation to begin. Set the
Override sensor at desired point for economizer
operation to end (factory default is 65ºF and 50ºF,
respectively).

Enthalpy Sensor with Override

t 5VSOVOJUQPXFSPGG%JTDPOOFDU

C7400 Solid State Enthalpy Sensor
from terminal So on the enthalpy
controller. Also, disconnect the

620 ohm resistor from
terminal Sr on the
enthalpy controller.
Turn unit power on. The
LED on the enthalpy
controller should light
and the energy recovery wheel should
not rotate.

t5VSOVOJUQPXFSPGG3FDPOOFDU
ohm resistor to terminal Sr on the
enthalpy controller. Turn unit power on.

The LED on the enthalpy controller should not light
and the energy recovery wheel should energize
and rotate.

If these steps provide the results described, the
enthalpy economizer is working properly.

t 5VSOVOJUQPXFSPGG3FDPOOFDU$4PMJE4UBUF

Enthalpy Sensor to terminal So.

Modulating the Wheel
In applications in which an internal heat gain is
present in the space, the rotational speed of the
energy wheel may be modulated (via variable
frequency drive) to avoid overheating the space
during the winter. The speed of the energy wheel
will be controlled in response to the discharge
temperature set point.

Sequence of Operation: The variable frequency
drive is fully programmed at the factory (refer to VFD
section for more information). A “call for cool” must
be field wired to the unit (terminals provided in unit -
refer to wiring diagram in unit control center) to allow
for initiation of economizer mode. When the space
calls for cooling, factory supplied controls will drive
the following wheel operations:

Where (T

OA

) is the outdoor air temperature set point,

(T

RA

) is the return air temperature set point, and (T

SA

)

is the supply air discharge thermostat set point.

Temperature

Sensor with

Override

Enthalpy

Sensor with

Override

T

OA

> T

RA

Wheel runs at full speed.

(maximum energy recovery)

T

OA

< T

RA

and

T

OA

> T

SA

Wheel is at minimum speed.

(no energy recovery)

T

OA

< T

RA

and

T

OA

< T

SA

Wheel will modulate to maintain

discharge temperature.

Enthalpy

Controller