G0524 Rip Saw
The following list outlines the electrical phase and 
voltage required to operate the rip saw, as well as 
the amperage draw of the motors:
Pre-Wired For 220V, 3-Phase
15 HP Main Motor .................................37 Amps
2 HP Feed Motor .....................................6 Amps
Rewired For 440V, 3-Phase
15 HP Main Motor ..............................18.5 Amps
2 HP Feed Motor .....................................3 Amps
Always check to see if the wires in your circuit 
are capable of handling the amperage draw from 
your machine, as well as any other machines that 
could be operating on the same circuit. If you are 
unsure, consult a qualified electrician. 
If the circuit breaker trips or the fuse blows regu-
larly, your machine may be operating on a cir-
cuit that is close to its amperage draw capacity. 
However, if an unusual amperage draw does not 
exist and a power failure still occurs, contact a 
qualified electrician.
Figure 1. Locking shut-off lever.
Use the following guidelines when choosing a 
circuit breaker (circuit breakers rated any higher 
are not adequate to protect the circuit):
220V 3-Phase ............................ 45 Amp, 3 Pole
440V 3-Phase ............................. 25 Amp, 3 Pole
Because of the high amperage draw from this 
machine, we recommend that you hardwire it 
directly to your circuit breaker and install a lock-
ing shut-off lever (
Figure 1) near the machine as
a way to quickly disconnect the power.
Circuit Capacity
Connection Type
Circuit Breaker
Voltage & Amperage
Draw
SECTION 3: CIRCUIT REQUIREMENTS