5.3.2 Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One of the Node names specified in
Section 5.1

Data_Type

Data type

Dig_input, Dig_output, -

Length

Length of Map Descriptor

1 to end of data block.

Address

Starting address of read block

The start bit number of the data of
interest

Command

The command id as given in the notes.

1, 4, 6, 10, 12, 16, 27, 29

Network*

The network number

0-255, 0

Zone*

The zone number

0-255, 0

Sector*

The sector number

1-255 or 0 to read the average smoke
level and highest alarms.

DA_Bit_Name*

Name of Data Array where data is to be
stored in the FieldServer. Used for
commands 10 and 16.

One of the Data Array names specified in
Section 4. Must be of type BIT, -

DA_Bit_Offset*

Starting location in Data Array. Used for
commands 10 and 16

0 to (Data_Array_Length -1) as specified
in Section 4, -

DA_Float_Name*

Name of Data Array where data is to be
stored in the FieldServer. Only used for
command 10.

One of the Data Array names specified in
Section 4. Must be of type FLOAT, -

DA_Float_Offset*

Starting location in Data Array. Only used
for command 10

0 to (Data_Array_Length -1) as specified
in Section 4, -

DA_Byte_Name*

Name of Data Array where data is to be
stored in the FieldServer. Only used for
command 16.

One of the Data Array names specified in
Section 4. Must be of type BYTE, -

DA_Byte_offset*

Starting location in Data Array. Only used
for command 16

0 to (Data_Array_Length -1) as specified
in Section 4, -

DA_Parameters

Name of Data Array where data is to be
stored in the FieldServer. Only used for
command 29.

One of the Data Array names specified in
Section 4. -

DA_Parameters_Offset

Starting location in Data Array. Only used
for command 29

0 to (Data_Array_Length -1) as specified
in Section 4, -