FieldServer FS-8700-43 User Manual
Page 26
FS-8700-43 VESDA Driver Manual
Page 26 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix A.8. VESDA mapping format for command 29 (Set Smoke Thresholds)
This command sets the Smoke Thresholds. The format for the data is as follows:
Appendix A.8.1.
Data Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array Up to 15 alphanumeric characters
Data_Format
Provides data format
Bit
Data_Array_Length Number of Data Objects
1
Appendix A.8.2.
Client Side Map Descriptors
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
Data_Array_Name
defined
in
Data_Array_Location
Starting location in Data Array
0
Function
Function of Client Map Descriptor.
AWT
Node_Name
Name of Node to fetch data from
One of the Node names specified in
Section 5.2.
Data_Type
Data type
-
Length
Length of Map Descriptor
1
Address
Starting address of read block
0
Command
The command ID
29
Network*
The network number
1-255, 0
Zone*
The zone number
1-255, 0
Sector*
The sector number
1-255, 0
DA_Parameters*
Name of Data Array where data is to be
stored in the FieldServer.
Data
Array
Name
defined
in
DA_Parameters_Offset* Starting location in Data Array.
0
Appendix A.8.3.
Data Block Description
10
10
1 indicates TRUE; 0 indicates FALSE
Bit offset Function
0
Alert Smoke Threshold Day
1
Action Smoke Threshold Day
2
Fire-1 Smoke Threshold Day
3
Fire-2 Smoke Threshold Day
4
Alert Smoke Threshold Night
5
Action Smoke Threshold Night
6
Fire-1 Smoke Threshold Night
7
Fire-2 Smoke Threshold Night
Bit offset Function
8
Sector Scanner for LaserScanner
Sector 1
9
Sector Scanner for LaserScanner
Sector 2
10
Sector Scanner for LaserScanner
Sector 3
11
Sector Scanner for LaserScanner
Sector 4