FieldServer FS-8700-43 User Manual
Page 24
FS-8700-43 VESDA Driver Manual
Page 24 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix A.7. VESDA mapping format for command 27 (Get Overall Smoke Thresholds)
This request returns the Overall Smoke Thresholds in a FLOAT data array. The format for the data is as follows:
Appendix A.7.1.
Data Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array Up to 15 alphanumeric characters
Data_Format
Provides data format
Float
Data_Array_Length Number of Data Objects
12
Appendix A.7.2.
Client Side Map Descriptors
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be stored
in the FieldServer
Data_Array_Name
defined
in
Data_Array_Location
Starting location in Data Array
0
Function
Function of Client Map Descriptor.
Rdbc
Node_Name
Name of Node to fetch data from
One of the Node names specified in
Section 5.2.
Data_Type
Data type
-
Length
Length of Map Descriptor
12
Address
Starting address of read block
0
Command
The command ID
27
Network*
The network number
1-255, 0
Zone*
The zone number
1-255, 0
Sector*
The sector number
1-255, 0