Appendix A.7. VESDA mapping format for command 27 (Get Overall Smoke Thresholds)

This request returns the Overall Smoke Thresholds in a FLOAT data array. The format for the data is as follows:

Appendix A.7.1.

Data Arrays

Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array Up to 15 alphanumeric characters

Data_Format

Provides data format

Float

Data_Array_Length Number of Data Objects

12

Appendix A.7.2.

Client Side Map Descriptors

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up to 32 alphanumeric characters

Data_Array_Name

Name of Data Array where data is to be stored
in the FieldServer

Data_Array_Name

defined

in

Appendix A.7.1

Data_Array_Location

Starting location in Data Array

0

Function

Function of Client Map Descriptor.

Rdbc

Node_Name

Name of Node to fetch data from

One of the Node names specified in
Section 5.2.

Data_Type

Data type

-

Length

Length of Map Descriptor

12

Address

Starting address of read block

0

Command

The command ID

27

Network*

The network number

1-255, 0

Zone*

The zone number

1-255, 0

Sector*

The sector number

1-255, 0