FieldServer FS-8700-43 User Manual
Page 11
FS-8700-43 VESDA Driver Manual
Page 11 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix A. Useful Features
Appendix A.1. VESDA mapping format for Command 1 (Set Operation)
This command is mandatory as it turns the VESDA system into a master slave relationship and is of type BIT. The
content of the data is irrelevant. The format for the data is as follows:
Appendix A.1.1.
Data Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array Up to 15 alphanumeric characters
Data_Format
Provides data format
BIT
Data_Array_Length Number of Data Objects
8
Appendix A.1.2.
Client Side Map Descriptors
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be stored
in the FieldServer
Data_Array_Name
defined
in
Function
Function of Client Map Descriptor.
Wrbc, Wrbx
Node_Name
Name of Node to fetch data from
One of the Node names specified in
Section 5.2.
Data_Type
Data type
Dig_Output
Length
Length of Map Descriptor
1-16 (must not overflow the data
array)
Address*
Starting address of read block
0-15, 0
Command
The command ID
1
Network*
The network number
1-255, 0
Zone*
The zone number
1-255, 0
Sector*
The sector number
1-255, 0
Appendix A.1.3.
Example
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Function , Data_Type , Node_Name , Address , Length , Command , Network , Zone , Sector
set_op_vesda_hli
, set_op
, Wrbc
, Dig_Output , VESDA_HLI , 0
, 8
, 1
, 0
, 0
, 0