Appendix A.2. VESDA mapping format for Command 4 (Zone Update)
This request returns the Current Zone Status in a BIT data array. The format for the data is as follows:
Appendix A.2.1.
Data Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array Up to 15 alphanumeric characters
Data_Format
Provides data format
BIT
Data_Array_Length Number of Data Objects
1 - 16
Appendix A.2.2.
Client Side Map Descriptors
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
Data_Array_Name defined in Section
Appendix A.2.1
Data_Array_Location
Starting location in Data Array
0 -15
Function
Function of Client Map Descriptor.
Rdbc
Node_Name
Name of Node to fetch data from
One of the Node names specified in
Section 5.2.
Data_Type
Data type
Dig_input
Length
Length of Map Descriptor
1-16 (must not overflow the data array)
Address
Starting address of read block
0-15
Command
The command ID
4
Network*
The network number
1-255, 0
Zone*
The zone number
1-255, 0
Sector*
The sector number
1-255, 0
Appendix A.2.3.
Data Block Description
4
BIT offset Function
BIT offset Function
0
Other Zone Info 8
Fault Power
1
Scanning
9
Fault Urgent
2
Autolearning
10
Fault Zone
3
Normalising
11
Fault System
4
Isolated
12
Alarm Fire2
5
Fault Filter
13
Alarm Fire1
6
Fault Airflow
14
Alarm Action
7
Fault Network
15
Alarm Alert
4
1 indicates TRUE; 0 indicates FALSE