FS-8700-132 Gamewell FCI-E3 Driver Manual

Page 9 of 20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.4

Map Descriptor Example 1 – Sensor / Module Events

If messages from Loop 1, Module 1 to 99 are received then the Map Descriptor in this example will be used for storage. If modules occur on more than one loop, one
Map Descriptor is required per loop. In this example the event type is set to ‘Alarm’ so only “Alarm” events will be stored. The “Event_Type” can be changed to suit the
required data. If all events are required, the parameter should be set to “Any”.

Example:

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name

, Data_Array_Name

, Data_Array_Offset

, Function

, Node_Name

, Event Type

, Point Type

, Relay/Loop/Zone Number

, Address

, Length

, Clear_on_Reset

ModuleData1

, DA_MODULE

, 0

, Passive_Client

, Panel-01

, Alarm

, Module

, 1

, 1

, 99

, Yes





















Unique Map
Descriptor
Names are
recommended.

Change this to
‘Sensor’ for
sensors.

Only Alarm
events will be
stored.

The Data Array
name and
starting location
that data should
be stored.

The driver listens
passively for
messages from
the Panel. It
cannot poll for
data.

The name of the
Node defined in
Section 5.2.

The address specifies
the starting Module
number and the Length
tells the driver the
range of Modules.
In this example: Module
1 to 99