Appendix A.3. Networked Panels.
The driver can processes messages and store data from multiple panels provided that:
The panels are connected in an FCI network and the panels are configured to report their events to the
main panel
The main panel is configured to send the Node of origin in a message preceding the event message.
Consult with FCI for information on how to achieve this.
Example of message sent by a panel that is networked. The driver is dependent on seeing the node of event origin
included in parenthesis before each event message.
Node02:
MISSING Acclimate L1S041 00:17:06 01/01/06
Node55: 1st Floor Lobby
DISCONNECT RSTRD Ion Detector L1S024 09:51:44 01/15/06
Local:
FIRST ALARM Photo Detector L1S001 09:24:52 12/01/06
The main panel is identified as ‘Local’. The driver interprets this as Node_ID=0.
To capture events from multiple networked panels a Node Descriptor is required for each panel with the
appropriate Node_ID. Each Node requires a set of Map Descriptors.