beautypg.com

FieldServer Optomux FS-8700-17 User Manual

Page 21

background image

FS-8700-17_Opto22.doc Manual

Page 19 of 24

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Read/
Write/
Both

COMMAND NAME

OPTO22_FORMAT
OPTION

MASTER
LENGTH
CONSIDERED
(See Notes)

NOTES

w

UPDATE ANALOG
OUTPUTS

3

Only specified module positions get
written. Data written gets extracted from
corresponding positions of data array.
This command can send a different value
to each output on a module. The values
are extracted from the Data Array specified
on the Map Descriptor Which modules get
sent a value is determined by the mask.
There are many ways of specifying the
mask.
The command ‘Write Analog Outputs’
sends a single analog value to one or more
points on the module.

r

READ ANALOG
INPUTS

3

Only specified module positions get read.
Data read gets put in corresponding
positions of Data Array.

r

READ AND
AVERAGE INPUT

4

Only one module position may be
specified. This position is averaged and the
result is put in the first element of the Data
Array The number of samples is specified
in modifier1 in the csv file.

w

START INPUT
AVERAGING

3

Only specified module positions get
affected by command. First element in
Data Array is sent as the number of
sample to average over.

r

READ AVERAGE
COMPLETE BITS

1

2

If format=Bit then length is considered
during storage as bits are unpacked into
Data Array. If format is non equal to bit
then result is written as a single value into
one array element. Retrieved data is stored
in standard Data Array.

r

READ INPUT
AVERAGE DATA

3

Only specified module positions get read.
Data read gets put in corresponding
positions of Data Array.

r

READ
TEMPERATURE
INPUTS

3

Only specified module positions get read.
Data read gets put in corresponding
positions of Data Array.

r

READ AVERAGE
TEMPERATURE
INPUTS

3

Only specified module positions get read.
Data read gets put in corresponding
positions of Data Array.