beautypg.com

Quickspecs – HP GS1280 User Manual

Page 58

background image

GS1280 Model 8
1 I/O Drawer, 1 SW
Shelf

GS1280 Model 16
1 I/O Drawer, 1 SW
Shelf

GS1280 Model 32
1 I/O Drawer, 1 SW
Shelf

GS1280 Model 64
1 I/O Drawer, 1 SW
Shelf

Power Required, Kva

3.5

5.7

10.1

18.7

Power Distribution Unit
(PDU) required for all
GS1280 Models 3X-H7606-
Ax

1 required; 2 for dual
AC

2 required; 4 for dual
AC

2 required, dual AC
included

2 required, dual AC
included

Power Distribution Unit
(PDU) required for GS 1280
Models 32 and 64, 3X-
H7606-Bx

Not applicable

Not applicable

2 required, dual AC
included

4 required, dual AC
included

Physical Characteristics

Dimensions (H x W x D)

79 x 24 x 47 in (200 x 60 120 cm) (one 41U Rack)

Shipping Dimensions

86 x 32 x 48 in (217 x 92.5 142 cm) (one 41U Rack)

GS1280 Model 8

GS1280 Model 16

GS1280 Model 32

GS1280 Model 64

Installed Weight, base system 870 lb (395 kg)

1,272 lb (577 kg)

2,118 lbs (961 kg)

4,800 lbs (2,176 kg)

Heat dissipation

Max Heat Output, Base Model
only, watts

3,405

6,810

14,820

28,440

Max heat Output, Base Model
only, Btu/hr

11,622

23,243

50,581

97,066

Typical Heat Output, Base
Model only, watts

2,430

3,700

8,000

14,800

Typical Heat Output, Base
Model only, Btu/hr

8,297

12,632

27,304

50,513

Airflow, cfm, minimum full
rack, each CPU rack

912

1,562

1,800

1,800 x 2 racks

Airflow, cfm, maximum full
rack, each CPU rack

1,404

2,454

3,400

3,400 x 2 racks

Airflow, cfm, minimum full
rack, power rack for Model 32
and 64

1,324

1,455

Airflow, cfm, maximum full
rack, power rack for Model 32
and 64

1,508

1,685

QuickSpecs

HP AlphaServer GS1280 Systems

Technical Specifications

DA - 11921 Worldwide — Version 24 — July 23, 2007