35

Figure 28 Grounding the switch by burying the grounding conductor into the earth ground

(1) Grounding screw

(2) Grounding cable

(3) Earth ground

(4) Joint

(5) Grounding conductor

(6) Switch rear panel

Grounding the switch in other grounding environments

Grounding an AC-powered switch

If the installation site has no grounding strips or earth ground, you ground an AC-powered switch through

the PE wire of the AC power supply.
Make sure the PE wire is well connected to the ground at the power distribution room or AC transformer

side, the switch PE terminal and the PE wire are well connected, and the three-wire input cable of the

grounding cable is used for the power supply cable. If the PE wire of the AC power supply is not

grounded at the power distribution room or AC transformer side, report the problem and reconstruct the
grounding system.

Figure 29 Grounding through an AC power PE wire

(1) Three-wire AC power input cable

(2) Switch rear panel

Grounding a DC-powered switch

If the installation site has no grounding strips or earth ground, you ground a DC-powered switch through
the return wire (RTN) of the DC power supply, and make sure this RTN wire is well connected to the

ground at the DC output of the DC power cabinet.