beautypg.com

Dunkirk DWB Series User Manual

Page 9

background image

Figure 5 - Boiler Clearances

9

4 - LOCATING BOILER

4.1 Boiler Location Considerations

• Ambient room temperature always above 32°F (0°C) to

prevent freezing.

• Approved for installation in closets.
• Protect gas ignition system components from water

(dripping, spraying, rain, etc.) during operation and

service (circulator replacement, control replacement,

etc.).

• Wall mount only.
• Access to outdoors to meet minimum and maximum

pipe lengths for combustion air and vent piping. See

section 6.

• Drainage of water (or water - antifreeze solution) during

boiler service or from safety relief valve discharge. See

section 5.

• Access to system water piping, gas supply, and electrical

service. See sections 5, 7 and 8.

• Clearances to combustible materials and service

clearances. See Table 1 and fi gure 5.

• The boiler must not be installed on carpeting.

A

D

F L O O R

F

F

Boiler

(Side View)

Boiler

(Front View)

F

B

C

Front

A

TABLE 1: BOILER CLEARANCES

Dimension

Combustible

Materials

(1)

Service

(1)(2)

Top (A)

16” (41cm)

16" (41cm)

Left Side (B))

0" (0 cm)

1” (3 cm)

Right Side (C)

0" (0 cm)

1” (3 cm)

Front (D)

0" (0 cm)

1" 3 cm)

Back (E)

0" (0 cm)

0” (0 cm)

Bottom (F)

0" (0 cm)

12" (30 cm)

Combustion Air/piping

0" (0 cm)

3/8" (1 cm)

Vent piping

6" (15 cm)

6" (15 cm)

(1)

Required distances measured from boiler jacket.

(2)

Service, proper operation clearance recommendation.