12

H. Extended DHW calls resulting in delayed response

to CH calls.

WARNING

Burn and Scald Hazard. Safety relief vlave

could discharge steam or hot water during

operation. Install discharge piping per these

instructions. Failure to do so could result in

death or serious injury.

!

5.5 Safety Relief Valve

NOTICE

Boiler rated at 43.5 psig (.30MPa) maximum allowable

working pressure. Boiler provided with 30 psig

(.21MPa) safety relief valve.

• Install safety relief valve using pipe fi ttings provided with

boiler. See fi gure 8.

• Install safety relief valve with spindle in vertical position.

• Do not install shutoff valve between boiler and safety

relief valve.

• Install discharge piping from safety relief valve. See

fi gure 9.

• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C)

or greater.

• Individual boiler discharge piping shall be independent

of other discharge piping.

Figure 7 - Indirect Tank Performance Chart

• System piping connected to heating coils located in air

handling unit exposed to refrigerated air circulation. Install

fl ow control valves or other automatic means to prevent

gravity circulation of boiler water during cooling cycle.

5.4 Storage Tank Connection For Domestic Hot

Water Production

• Unit’s electronic board is arranged for managing an

external storage tank for domestic hot water production.

• See fi gure 10 for hydronic plumbing.
• Make electrical connections as shown on wiring diagram

page 36.

• Boiler’s control system recognizes presence of hot water

tank probe and automatically confi gures DHW function,

activating display and controls.

• Match Indirect tank heat exchanger and boiler capacity.
• Indirect tank requires dedicated pump. See fi gure 7 and

indirect tank specifi cation to determine pump.

• Incorrect tank size or insuffi cient fl ow may result in:

F. Unsatisfactory indirect tank performance.
G. Boiler short cycling

5 - HYDRONIC PIPING

Figure 8 - Safety Relief Valve & Air Vent

(Viewed from front of boiler)

1” MPT

Coupling 1”

NPT

Nipple 1” x 5”

Tee 1” x 1” x ¾”

Safety Relief

Valve

Street Elbow ¾”