beautypg.com

Chb-100, Chb-130 – Dunkirk DWB Series User Manual

Page 34

background image

12.1 Ratings and Capacities

• Constructed and hydrostatically tested for maximum

allowable working pressure of 43.5 psig (pounds per
square inch gauge)

43.5 psig (.30MPa)

in accordance

with ASME Boiler and Pressure Vessel Code, Section IV,

Rules for Construction of Heating Boilers.

• USA - Input rates are derated 4% for each 1000 ft (300m)

above sea level, beyond 2000 ft (600m).

• CANADA - Ratings in table 13 used for elevations up to 2000

ft (600m) above sea level

- For elevations between 2000 ft (600m) and 4500

ft (1350m), derate 10% using high altitude kit.

- Contact Provincial authority having jurisdiction

for installations above 4500 feet (1350 m) above

sea level.

34

SEA LEVEL RATINGS

NATURAL AND PROPANE GASES

Size

Boiler Input Rate

(MBH)

(1)

Heating

Capacity

(MBH)

(1)(2)

Net AHRI

Rating, Water

(MBH)

(1)(3)

AFUE

(2)

Maximum

Minimum

CHB-100

100

31.5

85

73.0

85

CHB-130

130

43.5

110

96.0

85

(1)

1000 Btu/hr (British Thermal Units Per Hour)

(2)

Heating Capacity and AFUE (Annual Fuel Utilization Effi ciency) are based on DOE (Department of Energy) test

procedures.

(3)

Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for

installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,

etc.

12 - RATINGS AND CAPACITIES

Table 8 - Sea Level Ratings