5 > ip dongle installation & connection – Austin Hughes IPM-02 User Manual
Page 13
www.austin-hughes.com
UM-IPM-02-Q414V3
P.8
IP dongle for vertical PDU
Model :
IPD-02-S ( with SNMP feature )
Vertical IP dongle installation steps :
- slide the IP dongle on the plate above the meter
- plug the RJ-45 connector of IP dongle into the LINK port of the 1st level PDU meter
- use the CAT. 5 / 6 cable to connect IP dongle to network device
1st level
PDU meter
3rd level
PDU meter
2nd level
PDU meter
Cat 5 / 6 cable
Up to 20M
Cat 5 / 6 cable
Up to 20M
To LINK port of
the 1st PDU
IP dongle
Network Hub
To LAN port
IP Dongle Access to 16 PDU Levels
Patented IP Dongle provides IP remote access to the PDUs by a true network IP address chain.
Only 1 x IP dongle allows access to max. 16 PDUs in daisy chain - which is a highly effi cient ap-
plication for saving not only the IP remote accessories cost, but also the true IP addresses re-
quired on the PDU management.
Hot-Pluggable design facilitates the IP dongle installation. Simply integrate the IP Dongle to the
1st PDU, then the entire daisy chain group can be remote over IP. Hence, administrator can re-
motely access all PDUs in the daisy chain group by one single IP via the IP Dongle.
To LINK port
of next PDU
( Up to 16 levels )
< 1.5 > IP Dongle Installation & Connection