24 air purging – Pridiom Solar Series Installation Manual User Manual

Page 25

background image

24

AIR PURGING

When relocate the unit to another place,
perform evacuation using vacuum pump.
Make sure the refrigerant added into the air
conditioner is liquid form in any case.
(Not applicable to the units adopt freon R22 )

Open the valve stem until it hits against the
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
spanner or the like.
Valve stem cap tightening torque (See
Tightening torque table in previous page ).

Outdoor
unit

Indoor
unit

Refrigerant

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid side

A

C

D

B

Valve stem

Fig.59

Fig.60

When Using the Vacuum Pump

(For method of using a manifold valve, refer
to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D,

valve charge hose to a

charge port of the low-pressure valve on the
gas pipe side.

2. Connect the charge hose connection to the

vacuum pump.

3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After

slightly loose theflare nut

of the Lo valve on the gas pipe side
check that the air is entering(Operation noise

pump changes and a

com

meter indicates 0 instead of minus)

5. After the evacuation is complete, fully close

manifold valve and stop

the operation of the vacuum pump. Make
evacuation for 15 minutes or more

compound meter indicates

-76cmHg (-1x10 Pa).

6. Turn the stem of the packed valve B about

45 counterclockwise for 6~7 seconds after
the gas coming out, then tighten the flare nut
again. Make sure the pressure display in the
pressure indicator is a little higher than the
atmosphere pressure.

7. Remove the charge hose from the Low

pressure charge hose.

8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.

connect the manifold

starting evacuation,

and

of the vacuum

pound

the handle Lo of the

and check

that the

5

o

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Fig.61

Caution in handling the packed valve