Factory default settings of innotech devices, Default ethernet settings, Default device address and baud rate – Innotech Device Communications User Manual
Page 15: Table 2-2: default ethernet settings, Table 2-3: default innotech network settings
Page 7
Chapter 2 – Preliminary Information
DS 99.05 – Ethernet Setup Manual for Device Communications
2
Factory default settings of Innotech devices
All Innotech controllers and devices are configured at the factory with default Ethernet
settings that can be modified based on your network requirements. These settings
are required in order to correctly configure these devices so that correct functionality is
achieved within your network configuration. The following sections provide the default
Ethernet settings for devices equipped with an Ethernet port, and the default Innotech
network settings for devices that are covered in this document.
Device
Address
IP address
Subnet mask
Default
Gateway
Net comms
port
Genesis II
DHCP
AutoIP
DHCP
AutoIP – 169.168.x.x
DHCP or
255.255.255.0
DHCP or
0.0.0.0
20,000
MAXIM III
DHCP
AutoIP
DHCP
AutoIP – 169.168.x.x
DHCP
255.255.255.0
DHCP or
0.0.0.0
20,000
MAXIM 1010
DHCP
AutoIP
DHCP
AutoIP – 169.168.x.x
DHCP
255.255.255.0
DHCP or
0.0.0.0
20,000
IG01
Static
192.168.2.100
255.255.255.0
0.0.0.0
20,000
IG03
Static
192.168.2.100
255.255.255.0
0.0.0.0
20,000
IG04
Static
192.168.2.100
255.255.255.0
0.0.0.0
20,000
CONV-E
DHCP
AutoIP
DHCP
AutoIP – 169.168.x.x
DHCP
255.255.255.0
DHCP or
0.0.0.0
20,000
IWS01
Static
192.168.2.100
255.255.255.0
0.0.0.0
20,000
Default Ethernet settings
It is important to know the default Ethernet settings of your Innotech device(s) in order
to prepare the device(s) for deployment on your particular LAN. The table below shows
each applicable controller or device, and the associated factory default Ethernet settings.
Default Ethernet settings
Table 2-2:
Default device address and baud rate
The Innotech network device settings allow your device to communicate with iComm,
the Innotech communication software hub. Each device must have a unique device
address, and must be configured at the same baud rate as iComm software in order
to communicate on an Innotech network. The table below shows the default network
settings of each applicable controller or device as they are shipped from the factory.
Device
Innotech device address
Baud rate
Genesis II
1
57,600
MAXIM III
1
57,600
MAXIM 1010
1
57,600
IG01
2
57,600
IG03
2
57,600
IG04
2
57,600
CONV-E
N/A
9,600
Default Innotech network settings
Table 2-3:
**The IWS01 does not have a physical Innotech device
address.