beautypg.com

HT instruments MACROTEST 5035 User Manual

Page 64

background image

MACROTEST

5035

EN - 63

Global earth resistance (R

a15mA

)

Measuring range (

) Resolution

(

)

Accuracy

1

÷ 1999

1

±(5% rdg + 3 dgt)

Test current

15mA

Phase to earth test voltage

100

÷ 265V 50Hz ±0,5Hz


Earth resistance measurement with voltamperometric method

Measuring range (

) Resolution

(

)

Accuracy

0,01

÷ 19,99

0,01

±(5% rdg + 3 dgt)

20,0

ч 199,9

0,1

200

ч 1999

1

Test current

<10mA 77,5Hz

Open load test voltage

<20V RMS


Earth resistivity

ρ measurement

Measuring range (

) Resolution

(

m)

Accuracy

0.06

÷ 19,99 Ωm 0,01

Ωm

±(5% rdg + 3 dgt)

20.0

÷ 199.9 Ωm 0.1

Ωm

200

÷ 1999 Ωm 1

Ωm

2,00

÷ 19,99 kΩm 0.01

k

Ωm

20.0

÷ 125,5 kΩm (*)

0.1 k

Ωm

(*) with D = 10m
Test current

<10mA 77,5Hz

Open load test voltage

<20V RMS

9.1.1. Safety standards
The instrument complies with:

IEC/EN 61010-1 + A2(1997)

Product norms:

IEC/EN61557-1, -2, -3, -4, -5, -6

Insulation:

double insulation

Pollution level:

2

Inside use; max height:

2000m (6562 ft)

Overvoltage category:

CAT III 460V

∼ B1-B2-B3-B4 / 265V∼ to earth

9.1.2. General specifications
Mechanical features
Dimensions:

222(L) x 165(La) x 105(H)mm ; 9(L) x 6(W) x 4(H) in

Weight (batteries included):

1200g (42 ounces)

Power supply
Battery type:

6 batteries 1.5 V – LR6 – AA – AM3 – MN 1500

Low battery indication:

The symbol

is displayed when the battery

voltage is too low.

Battery life:

About 40 hours in stand-by or

500

Low

Ω tests or

250

R

ISO

tests 500V/500k

Ω or

1000 Loop, RCD o phase sequence tests

300 Earth or

ρ tests.

Display:

LCD custom 65mmx65mm

Memory: 350

tests

Serial interface:

optoisolated RS232 to download stored data to a PC.