beautypg.com

Reset of the instrument and default parameters – HT instruments MACROTEST 5035 User Manual

Page 59

background image

MACROTEST

5035

EN - 58

6. RESET OF THE INSTRUMENT AND DEFAULT PARAMETERS


BEFORE OF A RESET PROCEDURE DOWNLOAD THE STORED TESTS ON A PC

6.1. RESET

PROCEDURE

1. Press at the same time the keys DISP, CLR, RCL and then ignite the instrument.
2.

The screen nearby is displayed
for 5 seconds
, after which the
instrument

emits a sound signal

and then displays the screen
relative to the function selected
with the rotary switch.

es


ATTENTION:

the reset procedure will cancel all the stored tests and it will set the
default parameters in the instrument.


6.2. DEFAULT

PARAMETERS

After a RESET the default parameters set on the instrument are:

Function

Parameter

RESET default parameter

LOW

Mode AUTO

Calibration Offset

0

Mode R+/R- TIMER

TIMER is set at 1s

M

Mode MAN

Test voltage

500V

Mode TIMER

TIMER is set at 60s

RCD type

A/AC

Mode x1

Test differential current

30mA

Contact voltage limit

50V

LOOP Z

S

/I

K

Mode P-N

EARTH

ρ

Parameter DIST

DIST = 1

Memory

Parameter PLA

P = 1

Memory state

0