4.4. LOOP :

LINE/LOOP IMPEDANCE MEASUREMENT AND
PROSPECTIVE SHORT CIRCUIT CURRENT

Turn the

switch on LOOP

position.

Switch on the instrument.

The key

FUNC permits to select one of the following measuring modes

(which can be shown cyclically when pressing the key):

Mode

P-N” (the instrument measures the resistance between the phase

and neutral conductors and calculates the phase to neutral prospective
short circuit current).

Mode

P-P” (the instrument measures the resistance between two phase

conductors and calculates the phase to phase prospective short circuit
current).

Mode “

P-PE” (the instrument measures the resistance between the

phase and protective conductors and calculates the phase to earth
prospective short circuit current).

Mode “

” (the instrument detects the phase sequence and measures

the three delta voltages: L1-2, L2-3, L3-1).

CAUTION

The display of

“Measuring” means that the instrument is measuring. During

this phase never disconnect test leads.


4.4.1. High resolution Impedance measurement (0.1m

)

Macrotest5035 is connectable to an external

optional accessory (IMP57) useful for high

resolution impedance measurement close to a power transformer.
The high Resolution impedance measurement is available inside the

LOOP P-P, P-N, P-PE

modes by mean

Un/I∆n key.

If You enable the High Resolution Impedance Measurement mode without connecting IMP57
the following screen will be displayed:

LOW

LOOP

o

!!

no


con ins


!

For further details regarding IMP57 use and technical characteristics please refer to IMP57
user's manual or HT web site

www. htitalia.com.