8. TECHNICAL SPECIFICATIONS

cations

Power supply

24 Vac +10 to -15%, 50/60Hz, 1 VA
22 to 35 Vdc, 0.5W
Class 2 safety power supply
Min. cable cross-section 0.5 mm

2

.

Power supply compatible with compactSteam (G – G0)

Operating temperature

0 to 60°C, 32 to 140°F, 10 to 90% rH not-condensing

Storage temperature

-20 to 70°C, -4 to 140°F, 10 to 90% rH not-condensing

Precision of inside temperature measurement

±1°C from 0 to 60 °C, ±2°F from 32 to 140 °F

Precision of outside temperature measurement

± 1.5°C from 0 to 40°C ± 2.0°C from -40 to 0 and 40 to 80 °C
± 3°F from 32 to 104°F ± 4°F from -40 to 32and 104 to 176 °F

0 to 10 V analogue output, not isolated, for proportional control

precision ±5%
max load 5 kΩ, max current 2 mA

Relay approval

EN60730-1: NO 1(1)A 250 Vac cos = 0.4, 100,000 cycles
UL-873: NO 1A resistive 24 Vac, 30 Vdc, 100,000 cycles
PILOT DUTY: 24 Vac, peak 15 A, continuous 1 A, 30,000 cycles

Precision of humidity measurement (in models where featured)

range 10 to 90%%

± 3% rH at 25°C , 77 °F
± 5% rH 0 to 60°C, 32 to 140°F

Dimensions (mm):

135x86x36mm

Tab. 5.a

8.2 Wiring

:

n

o

i

s

r

e

v

d

e

t

a

l

o

s

i-

n

o

N

t

u

p

n

i

l

a

ti

g

i

D

direct connection of the voltage-free contact; contact closing current: 3 to 5 mA

.

Isolated version:

with external power supply to 24 Vac contact: class 2 safety external power supply separate from the 24
Vac power supply to the instrument

Outside temperature sensor connection

with standard sensor (10 K 25 °C B=3435):

Maximum length: 30 m, min. cable cross-section 0.5 mm

2

.

Digital input connection

Maximum length 10 m, min. cable cross-section 0.5 mm

2

.

Analogue output connection

Maximum length 10 m, min. cable cross-section 0.5 mm

2

.

Relay output connections:

Maximum length 30 m, cable cross-section from 1.5 to 2.5 mm

2

, class 2 reinforced insulation from the

instrument.
Basic insulation between the relays.

cations for connections:

Use copper wires approved for a temperature of 75 C.

To tighten the terminals, apply a torque of 7 Lb/In for the black terminals (SAURO)
To use the instrument in compliance with UL-873, a load with a maximum voltage 24 Vac, class 2, can be
connected to the relay output.

Tab. 5.b

Warning:

All the connections, except for the relays, must be

connected to very low voltage circuits with reinforced insulation.

10