Intelligent Motion Systems UDAS-1001E User Manual
Page 62
C-7
Analog Output Channel 0 Offset and Gain
Analog Output Channel 0 Offset and Gain
1.
Verify the termination panel is attached to a 50-pin connector of a UDAS unit. Begin with step
2 if the unit has built-in termination.
2.
Attach a multimeter to analog output channel 0.
3.
Use SYSCHECK or other software to set analog output channel 0 to -10.000 V.
4.
Adjust Pot R26 for -10.000 V (±0.2 mV).
5.
Set analog output channel 0 to 9.9951 V.
6.
Adjust Pot R36 for 9.9951 V (±0.2 mV).
7.
Repeat these steps to verify the results.
Analog Output Channel 1 Offset and Gain
Analog Output Channel 1 Offset and Gain
1.
Verify the termination panel is attached to a 50-pin connector of a UDAS unit.
2.
Attach a multimeter to analog output channel 1.
3.
Use SYSCHECK or your calibration software to set analog output channel 1 to -10.000 V.
4.
Adjust Pot R24 for -10.000 V (±0.2 mV).
5.
Set analog output channel 1 to 9.9951 V.
6.
Adjust Pot R25 for 9.9951 V (±0.2 mV).
7.
Repeat these steps to verify the results.