Tumblers – T30 and T45

14

4-08-43

NOTE: Do not install wire mesh or screen in

exhaust duct opening to avoid lint build-up or

impacting proper discharge of air from tumblers.

NOTE: Where exhaust duct pierces a combustible

wall or ceiling, the opening must be sized per local

codes.

NOTE: Inside of duct must be smooth. Do not use

sheet metal screws to join sections.

Consult your local building code for regulations which

may also apply.

Manifold Venting

While it is preferable to exhaust tumblers individually

to the outdoors, a main collector duct may be used if it

is sized according to Figure 4 or Figure 5. This

illustration indicates minimum diameters, and should

be increased if the collector length exceeds 14 feet (4.3

m) and two 90° elbows. The diameter of a round duct

must be increased by 10% for each additional 20 feet

(6.1 m). Cross sectional area of a rectangular or square

duct must be increased 20% for each additional 20 feet

(6.1 m). Refer to Table 2 or Table 3 to determine

equivalent ducting sizing. The collector duct may be

rectangular or square in cross section, as long as the

area is not reduced. Provisions MUST be made for lint

removal and cleaning of the collector duct.

TMB2103N

1

Removable strip of panel in framing wall to permit removal of tumbler from framing wall

2

Partition or bulkhead

3

Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)

4

2 in. (51 mm) minimum clearance on both sides of duct

5

Exhaust airflow – maximum length of duct: 14 ft. (4.3 m)