Henny Penny OFE-341 User Manual
Page 6
Model OFE/OFG/OEA/OGA-341, 342
2-7. GAS LEAK TEST
Prior to turning the gas supply on, be sure the gas valve
knob on the gas control valve is in the OFF position.
Upon initial installation, and after moving the unit, the piping
and fittings should be checked for gas leaks. A simple
checking method is to turn on the gas and brush all
connections with a soap solution. If bubbles occur, it
indicates escaping gas.
To avoid fire or explosion, never use a lighted match or
open flame to test for gas leaks. ignited gas could result
in severe personal injury and/or property damage.
2-8. PRESSURE REGULATOR
The gas pressure regulator on the automatic gas valve is
factory set as follows:
• Natural: 3.5 inches water column (8.7 mbar).
• Propane 10.0 inches water column (24.9 mbar).
The gas pressure regulator has been set by Henny
Penny and is not to be adjusted by the user.
2-9. ELECTRICAL
• 120 V, 60 Hz., 12 A, 1 PH
REQUIREMENTS
• 230 V, 50 Hz., 6.2 A, 1 PH
OFG/OGA-340 SERIES
The 120 V gas fry station requires a 3 wire grounded
(Earthed) service and is supplied with a grounded cord and
plug. Any 230-volt plug used on the 230-volt unit must
conform to all local, state, and national codes.
To avoid electrical shock, this appliance must be
equipped with an external circuit breaker which will
disconnect all ungrounded (unearthed) conductors.
The main power switch on this appliance does not
disconnect all line conductors.
903
2-6