As you can see from Fig 3-3, if you set parameters A11 and A12 other than “0”, you should set the target

value inside the valid range of the vertical axis. Otherwise it is not possible to achieve stable performance

because there is no feedback value. That means the inverter will either output maximum frequency or

stop, or it will output lower limit frequency continuously if it is set.

(6) Scale Conversion

Using this function, you can set and display the target value and display the feedback value in the

actual units of the process variable. Set the parameters individually relative to 100% of feedback value.

With the factory default setting, the input and display value is based on 0 - 100%.

Example : In case of (a) in Fig.3-3, 20mA of feedback corresponds to 100% of PID internal calculation. For

instance, if actual flow at 20mA of feedback is 60 [m

3

/ min], you set the parameter to 0.6 (=60 /

100) in function mode A75. Then you can get the actual feedback value on the monitor mode

d04, and you can also set the target value by actual value of the control system.

100

%

25

0

10V

2V

0

20mA

(a) A13 =

20%

A14 =

100%

A11 =

25%

A12 =

100%

4mA

0

100%

20%

0

100

75

%

0

10V

5V

0

20mA

Fig. 3-3 Setting Active Range : Example 2

(b) A13 = 0%
A14 =

50%

A11 = 0%
A12 =

75%

10mA

0

100%

50%

0

100

%

0

10V

2.5V

0

20mA

(c) A13 =

25%

A14 =

75%

A11 =

25%

A12 =

75%

5mA

0

100%

25%

0

7.5V

15mA

75%

75

25

Fig. 3-4 Example of Scale Conversion

L100/

SJ100

Target

Feedback

DC 4 -20mA

Fan

(a) Factory setting

Motor

unit = [%]

Monitor d01 =

0 - 100%

Monitor F01 =

0 - 100[%]

(b) A75 = 0.6

L100/

SJ100

Target

Monitor d01 =

0 - 60m

3

/min

Monitor F01 =

0 - 60[m

3

/min]

unit = [m

3

/min]

Feedback

DC 4 -20mA