SJ100/L100 / PID / 4

SJ100/L100 series inverters have integrated PID control, which is indicated by the dotted line in Fig. 2-1.

You can use PID control by setting a target value and providing a feedback signal.

The example in Fig. 2-2 shows a connection diagram for ventilation flow control in a fan application.

(1) P : Proportional Control

This controls the output frequency so that output frequency and deviation have a proportional relation.

The coefficient of deviation and output frequency (expressed in %) is called Proportional Gain (K

p

). This

parameter can be set under function [A71].

Fig. 2-3 shows the relationship between deviation and output frequency. If you set a high value of K

p

,

the response of the system to a rapid change in deviation is fast. However, if K

p

is too high, the system

can become unstable.

SJ100/

L100

Target

Feedback

Transducer

(DC0-10V, 4-20mA)

Flow volume sensor

Fan

Motor

Fig. 2-2 Wiring example for flow control application

100% of output frequency of above figure is equivalent to maximum output frequency.

K

p

can be chosen between 0.2 and 5.0 in function [A71].

4 bit of digital

input signal

Fig. 2-3 Relation between deviation and output frequency of SJ100/L100

Max. frequency <--- 100

75

50

Output

frequency

(%)

25

100

75

50

25

0

Deviation(%)

K

p

=2

K

p

=1

K

p

=0.75

Kp=0.5

Kp=0.25

0 2

5 0

.

.

K p