(3) Scale Conversion Factor Setting

Set this factor according to your application, e.g. flow, pressure, temperature and so on. For a detailed

explanation, please refer to item (6) on page 9.

(4) Target Input by Digital Input Signal

Please refer to the following when changing the target with the digital input signal (4 bit max.).

(a) Input terminal assignment

L100 series inverters have five intelligent input terminals. The SJ100 series have six. Assign “CF1”,

“CF2”, “CF3” and “CF4” to 4 of the intelligent input terminals. This assignment is done with function

numbers C01 to C05 (or C06 for SJ100), which correspond to terminals 1 to 5 (or 6) on the I/O

terminal.

(b) Setting each target value

Next, set the required number of targets (up to 16 targets maximum) according to the following table

(Table 3-3). Set them using functions A21 to A35 which correspond to target 0 to 15. A20 and F01

correspond to a target 0. Please note that in case a scale conversion ratio is set, you should set those

targets as converted value according to this ratio.

Table 3-3 Multi-stage Target Input (1 : ON, 0 : OFF)

No.

CF4

CF3

CF2

CF1

Referred Target number (Function number to be inputted)

1

0

0

0

0

Target 0

(A20 or F01)

2

0

0

0

1

Target 1

(A21)

3

0

0

1

0

Target 2

(A22)

4

0

0

1

1

Target 3

(A23)

5

0

1

0

0

Target 4

(A24)

6

0

1

0

1

Target 5

(A25)

7

0

1

1

0

Target 6

(A26)

8

0

1

1

1

Target 7

(A27)

9

1

0

0

0

Target 8

(A28)

10

1

0

0

1

Target 9

(A29)

11

1

0

1

0

Target 10

(A30)

12

1

0

1

1

Target 11

(A31)

13

1

1

0

0

Target 12

(A32)

14

1

1

0

1

Target 13

(A33)

15

1

1

1

0

Target 14

(A34)

16

1

1

1

1

Target 15

(A35)

Note: If you need only 4 targets, you would only use CF1 and CF2.

(5) PID Mode Selection

Set PID mode selection A71 to “01”. You can also set this function first.