3. HOW TO USE

3-1 Structure & Parameters

(1) Control Mode

Integrated operator

A71 : 00 / 01

DOP, DRW

F43 : PID SW ON / OFF

SJ100/L100 series inverters feature the following two control modes:

l Frequency control mode

l PID control mode

These can be selected by “PID function selection (A71)”.

Frequency control mode is the typical control mode of standard frequency inverters which enables

you to give a frequency command to the inverter from either the operator panel, or by analog voltage or

current, or by 4 bit digital command from the control terminals.

In the PID control mode, an output frequency is set automatically such that the deviation between

target value and feedback value approaches zero.

(2) Parameters

Fig. 3-1 shows the relation between control block diagram of PID control and each parameter. Function

numbers shown in the figure are based on the commands from the integrated operator of the inverter.

+

+

+

Selectable by

A01

Frequency
command

I Gain : A73

P Gain : A72

D Gain : A74

Operator
Multi stage setting

Maximum frequency is
considered to be
100%

Pot-meter
Analog voltage input
Analog current input

10V (20mA) is
considered to be 100%

Fig. 3-1 control block diagram of PID control

Scale

conversion

A75

Target value display

: F01

Target

Analog voltage input
Analog current input

Voltage / current
selection is done by

A76

Feedback

100%

A12

A11

0

A14

A13

Operation area

FB value display :

d04

Scale

conversion

A75

Reverse scale

conversion

A75

-1