Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. Q • 11/08

26

Top Vent - Vertical Termination

No Elbow

Figure 7.6

Note: If installing a vertical vent/termination off the top of the
appliance, the fl ue restrictor should be used.

V

1

V

1

= 50 ft. Max. (15.2 m)

V

1

= 3 ft. Min. (914 mm)

Installing the fl ue restrictor

Figure 7.7

FLUE RESTRICTOR

Figure 7.8 fl ue restrictor

BREAK

HERE

1. Note location of fl ue restrictor (see Figure 7.7). Break

the fl ue restrictor into two pieces. Do this by bending the
part back and forth until it breaks (see Figure 7.8).

2. Match the amount of vertical in the system with the chart

to fi nd the appropriate position to set the fl ue restrictor
(see Figure 7.9).

1 2 3 4 5

SETTING

1 2 3 4 5

Figure 7.10

3. Center the fl ue restrictor on vent and secure in place

by using two self-tapping screws (see Figure 7.10).

Figure 7.9

- CHART -

Vertical

Top Vent

NG

Top Vent

LP

4’

1-1

No Restrictor

8’

2-2

1-2

15’

3-3

3-2

20’

3-4

3-3

25’

3-4

3-3

30’

4-4

3-4

35’

4-4

3-4

40’

5-4

4-4

45’

5-4

4-4

50’

5-4

4-4